Back by Page

RP114Heavy Duty Seal

Fire ApprovedFires exceeding 600ºC and smoke exceeding 200ºCWeather AcousticInsects and VerminLightEnergy, Draughts and Dust


RP114 is a door bottom intumescent fire and hot smoke seal that is designed to salvage non compliant fire doors where clearances exceed 10mm under fire doors as per AS/NZS 1905.1.

The simple retro-fit design avoids costly door replacement and the need to remove the door during installation.

RP114 is approved for use on leading proprietary fire doors.
Note: RP114 should just clear the floor during door opening and closing. To avoid the seal fouling on uneven or sloping surfaces the finned gasket portion should engage an approved Raven threshold plate. This will enhance the other icon sealing functions.

Location Bottom of Fire and smoke doors.

Min/Max Gap 14mm to 20mm (without Raven threshold plate)

Seal Sizes Available 820mm, 915mm, 1220mm.

Standard Finish Aluminium anodised 15 microns. Satin Clear (silver) or Bronze finish.

Fixing method Simply cut seal to length. Zinc plated cross recess head ST screws of the appropriate size are supplied.

Seal Material Intumescent infill, S.E. flexible PVC cover strip and finned gasket.

Used in Conjunction with approved Raven door frame seals and threshold plates.

Approvals
Fire & Smoke AUS/NZ: Conforms to BCA Spec. C3.4. Tested to AS 1530.4 & AS/NZS 1905.1.
UK/EU: Conforms to Approved Document B. (Tests above are similar to BS EN 1634.1, BS 476 Part 20 & 22).
 
New product
RP114-profile
RP114 on the door bottom




Pricing Information

Back by PageTop of Page